Introduction - Organization
For the needs of the CERN users
to test LHC equipment under magnetic field a facility with a large dipole magnet was created in the North Area Experimental Hall (EHN1). The
large dipole magnet, called MNP22, is located at the Jura side in the EHN1 hall
(building 887) and downstream the final dump of the H2 beam line.
Organization
To coordinate the activities,
requests for the use of the facility, the installation, and technical
support for the facility is under responsibility of EN-MEF-LE section.
For questions about the magnet (control) you can contact
Simon Mataguez (mobile: 165711).
MNP22 facility Schedule for 2012
Points to remember:
-
During
their tests, the users are responsible for their security in the
dedicated area. The different apparatus used must follow the electrical
safety instructions (e.g.: high voltage, grounded correctly, etc...).
Depending on the size and nature of the tests a safety inspection may be
needed before. In case of doubts please contact
Christopher Griggs (tel:
73314, mobile: 163948, dso.ph@cern.ch) , the DSO of the PH Dept. or the
TSO of the EHN1
building Mickael Jeckel.
-
It's very
important that you maintain the area clean in particular at the end of
your tests. Material that will be left there, in particularly
unidentified, risk to be thrown away without notice.
-
It is not guaranteed that the
magnet will be operational during the accelerator shutdown (typically
November to March each year). This because the magnet needs the cooling
water to operate and consumes quite some current so it may be switched
off during critical days. It is a good practice in case of doubts to
contact the technical responsible for the facility.
Area Layout
In the photos below the area and
the magnet are shown. The magnet has a large aperture of 500mm (to be
verified). The magnet can be operated by a dedicated terminal located in a
counting room opposite the magnet:
HNA-184 (887-R-B84). code 10101.
The magnetic field
The magnetic
field map has been measured in 2003 by the ALICE TOF group and is shown in
the figure below.
 |
The magnet is powered by the power converter NR21-029.
- the maximum current is : + / - 1000 A
- Presently only DC mode is possible
|
Operational Issues
Information concerning the magnet
operation can be found below:
Setting up to start the magnet:
Before starting, the availability and well functioning of
the following systems should be verified:
-
Control system used
via the windows PC: CWO-HNA184-MNP located in the counting room HNA-184
(887-R-B84) opposite to the magnet area. What needs to be done:
Login into the computer using
your NICE account. In case you
experience network problems you should
contact the CERN network support service
and ask for help or advice 77777.
Launch the Lab View application called "MNP22" by either the desktop shortcut or via Start/All Programs/MNP22. Once the
program started the initial control panel should be visible.
-
Power converter NR21-029
should be operational. This can be verified using the
control panel in the LabView application:
-
you select NR21-029
-
check on the STATUS panel that the power is on
REMOTE and not on LOCAL mode
-
check on the DETAILED STATUS panel there is no
fault
-
do a RESET following by an UPDATE STATUS, if you
have any fault in the DETAILED STATUS section,
The power converter is under the
TE/EPC responsibility. For any problems call the
First Line service (16 3668).
Note:
-
Because there is no automatic update, you have to
do an UPDATE STATUS after each action.
-
It takes one cycle length (of the SPS machine
which is about 20sec) before each command to the magnet is executed.
This is a feature of the system which is hard to change.
-
Cooling water of the magnet should be operational. This can be done:
-
by visual
check in the
pressure indicator situated on the side of the magnet,
-
or via the Lab View application under the
'Detailed status panel'. If the cooling is not OK you get the
following message: "water-pressure".
The cooling water distribution and in general the servicing of the
magnet itself is under the
TE/MSC
section's responsibility. The expert to call in case of problems is
Michel Ros Francisca (mobile: 16 3364).
-
Finally, the "Red Button" installed ON the magnet itself should be in the un-locked
position. In case it is pushed, it inhibits the power converter and no
current can be set. An error in the Lab View screen is shown. If pushed,
to release it it must be turned clockwise (to be verified).
- Important info:
As mentioned above, operation of
the magnet during the shutdown is not guaranteed. There are also cases (like
critical days) where either the power supply or the cooling water circuits
are scheduled to be unavailable. Therefore, before contacting various
experts and making them loose their time Simon Mataguez should be contacted
to verify that indeed the magnet CAN be operational.
Starting a current value:
This is done using
the Lab View application from the dedicated terminal in the MNP22 control
room. The steps to follow to set a current in the magnet:
With the STB button put the power converter NR21-029 in
Standby mode ( Main Circuit Breaker = ON and Switch Position = NEUTRAL)
SET CURRENT = 'your desired value'
START the converter (MCB = ON and Switch Position =
NORMAL or INVERTED depending of the sign of the current)
for any new current values, go to step-2 and do a
SET CURRENT comment again.
Note: The DAC Value in the panel Setting Current
section is an unsigned value - Example of a
good state.
Ending your test - switch magnet OFF
This also done using the Lab View application. The steps to follow are:
With the STB button put the power converter NR21-029 in Standby mode ( MCB = ON and Switch Position = NEUTRAL)
With the STOP button set the MCB = OFF
Good luck and enjoy your stay at the facility !!!!
|